Compare
Clear
Hyundai IEEE40-36-324TS
Get full specifications on Hyundai IEEE40-36-324TS
- General Details
- Technical Details
- Area Classification
- Performance
- Speed Range
- Misc
- Enclosure: TEFC
- HP: 40
- Pole: 2
- RPM: 3600
- Frame: 324TS
- Motor Standards: IEEE-841, VERSION 2009, NEMA, CSA
- Phase: 3
- Hertz: 60 HZ
- Enclosure: TEFC
- HP: 40
- Pole: 2
- RPM: 3600
- Frame: 324TS
- Full Load Amps: 45.5 A
- Weight: 530 LBS
- Nema Design: B
- Duty: S1 / CONTINUOUS
- Insulation Class: F CLASS N VARNISH
- Ambient Teperature: 40° C
- Service Factor: 1.15
- Ingress Protection: IP56
- Elevation: 3300 FT. ABOVE SEA LEVEL
- Voltage: 460
- Full Load Speed: 3560 RPM
- Efficiency 100: 92.4 %
- Efficiency 75: 92.6 %
- Efficiency 50: 91.4 %
- Power Factor 100: 89.5 %
- Power Factor 75: 88.5 %
- Power Factor 50: 86.0 %
- Locked Rotor Torque: 160 %
- Breakdown Torque: 230 %
- Locked Rotor Current: 650 %
- CT: 10:1
- VT: 1000:1
- Voltage: 460
IEEE40-36-324TS Crossovers
Siemens 1LE24213BA112AA3
- Category: Severe Duty
- HP: 40
- Voltage: 460
- Frame: 324TS
- Enclosure: TEFC
- Efficiency: Premium Efficient
- Hertz: 60
- RPM: 3600
Teco Westinghouse (Canada) MD0402
- Category: Severe Duty
- HP: 40
- Voltage: 460
- Frame: 324TS
- Enclosure: TEFC
- Efficiency: Premium Efficiency
- Hertz: 60
- RPM: 3600
Schedule a meeting
Follow the link below to learn more about the system and schedule a meeting with one of our experts
Book now